  • Filtering of harmonics 3rd, 5th, 7th, 9th, 15th, 17th, 19th

Products in this family

Reference Description Rating Input voltage Output voltage
C25D10-0 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 10 kVA 400 V 400 V + N
C25D12.5-0 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 12,5 kVA 400 V 400 V + N
C25D16-0 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 16 kVA 400 V 400 V + N
C25D20-0 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 20 kVA 400 V 400 V + N
C25D25-0 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 25 kVA 400 V 400 V + N
C25D31.5-0 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 31,5 kVA 400 V 400 V + N
C25D40-0 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 40 kVA 400 V 400 V + N
C25D50-0 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 50 kVA 400 V 400 V + N
C25D63-0 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 63 kVA 400 V 400 V + N
C25D80-0 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 80 kVA 400 V 400 V + N
C25D100-0 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 100 kVA 400 V 400 V + N
C25D125-0 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 125 kVA 400 V 400 V + N
C25D160-0 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 160 kVA 400 V 400 V + N
C25D10-180 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 10 kVA 400 V + N 400 V + N
C25D12.5-180 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 12,5 kVA 400 V + N 400 V + N
C25D16-180 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 16 kVA 400 V + N 400 V + N
C25D20-180 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 20 kVA 400 V + N 400 V + N
C25D25-180 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 25 kVA 400 V + N 400 V + N
C25D31.5-180 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 31,5 kVA 400 V + N 400 V + N
C25D40-180 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 40 kVA 400 V + N 400 V + N
C25D50-180 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 50 kVA 400 V + N 400 V + N
C25D63-180 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 63 kVA 400 V + N 400 V + N
C25D80-180 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 80 kVA 400 V + N 400 V + N
C25D100-180 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 100 kVA 400 V + N 400 V + N
C25D125-180 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 125 kVA 400 V + N 400 V + N
C25D160-180 C25D-0/C25D-180 - Harmonic filter for office buildings, with galvanic separation 160 kVA 400 V + N 400 V + N

Dimensions and weights

Reference Rating Dimensions mm Weight kg Fig
A B C D E Ø
C25D10-0 10 kVA 595 415 708 375 350 12 106
C25D12.5-0 12,5 kVA 595 415 708 375 350 12 126
C25D16-0 16 kVA 595 415 708 375 350 12 149
C25D20-0 20 kVA 595 415 708 375 350 12 175
C25D25-0 25 kVA 789 490 965 450 415 13 216
C25D31.5-0 31,5 kVA 789 490 965 450 415 13 254
C25D40-0 40 kVA 789 490 965 450 415 13 292
C25D50-0 50 kVA 985 575 1310 475 470 18 418
C25D63-0 63 kVA 985 575 1310 475 470 18 526
C25D80-0 80 kVA 985 575 1310 475 470 18 578
C25D100-0 100 kVA 985 575 1310 475 470 18 623
C25D125-0 125 kVA 1195 635 1620 535 690 18 750
C25D160-0 160 kVA 1195 635 1620 535 690 18 834
C25D10-180 10 kVA 595 415 708 375 350 12 106
C25D12.5-180 12,5 kVA 595 415 708 375 350 12 126
C25D16-180 16 kVA 595 415 708 375 350 12 149
C25D20-180 20 kVA 595 415 708 375 350 12 175
C25D25-180 25 kVA 789 490 965 450 415 13 216
C25D31.5-180 31,5 kVA 789 490 965 450 415 13 254
C25D40-180 40 kVA 789 490 965 450 415 13 292
C25D50-180 50 kVA 985 575 1310 475 470 18 418
C25D63-180 63 kVA 985 575 1310 475 470 18 526
C25D80-180 80 kVA 985 575 1310 475 470 18 578
C25D100-180 100 kVA 985 575 1310 475 470 18 623
C25D125-180 125 kVA 1195 635 1620 535 690 18 750
C25D160-180 160 kVA 1195 635 1620 535 690 18 834

Technical characteristics

Isolation Class H - 180ºC
Winding Class HC - 200ºC
Cover In metal enclosure, epoxy polyester painted
Filtering of harmonics coming from the load 3, 9, 15 with one compensator
3, 5, 7, 9, 15, 17, 19 combining C25D-0/180
Frequency 50-60 Hz
Protection degree IP-23
Includes Lifting eyebolts as from 25kVA
Set of wheels (optional) RUE060 wheels from 10 kVA to 40kVA
RUE125 wheels from 50kVA to 160kVA
Link to wheels prices
Maximum admissible 3rd harmonic in voltage - -
Maximum admissible THD-I 90 %
Standards IEC/EN/UNE-EN 60076 - 60726, CE
IEC/EN/UNE-EN 61000-3-2 CE,
IEC/EN/UNE-EN 61000-3-4 IEE 519, CE
Reduction of phase current up to 15 % with one compensator
45 % combining C25D-0/180
Reduction of neutral current and neutral-earth volt. up to 90 %
Reduction THD-I and THD-V up to THD-I: 45 %, THD-V: 40% with one comensator
THD-I: 85 %, THD-V: 65% combininig C25D-0 and C25D-180
Cooling ANAN
Ambient temperature 30ºC
Test voltage 3 kV (1 min, 50 Hz)
  • Line voltage: C25D-0: 400 V, C25D-180: 400 V+N
  • Note: For selection, please consult the application guide