Go to: Content » | Main menu » | Information menu »


Secondary menu

R - Single phase cast resin line inductor

For harmonic filtering. Line voltage 220 - 260 V.

Series: 
R
R - Single phase cast resin line inductor
If you need more information you can contact us. If you are not logged in you can log in here
  • Advantages of cast resin technique:
    • Protection against corrosive environments
    • Suitable for elevated vibration levels
    • No damange of wire isolation due to current peaks
    • Reduction of noise and internal vibrations

Products in this family

Reference Description In (A) Motor rating L (mH)
R2.5 single phase cast resin line inductor 2,5 A 0,23 kW / 0,31 CV 8,785
R4 single phase cast resin line inductor 4 A 0,38 kW / 0,5 CV 5,491
R5 single phase cast resin line inductor 5 A 0,46 kW / 0,6 CV 4,393
R6.3 single phase cast resin line inductor 6,3 A 0,55 kW / 0,75 CV 3,486
R8 single phase cast resin line inductor 8 A 0,75 kW / 1 CV 2,745
R10 single phase cast resin line inductor 10 A 1,1 kW / 1,5 CV 2,196
R12.5 single phase cast resin line inductor 12,5 A 1,5 kW / 2 CV 1,757
R16 single phase cast resin line inductor 16 A 1,85 kW / 2,5 CV 1,373
R20 single phase cast resin line inductor 20 A 2,2 kW / 3 CV 1,098
R25 single phase cast resin line inductor 25 A 3 kW / 4 CV 0,879
R31.5 single phase cast resin line inductor 31,5 A 4 kW / 5,5 CV 0,697
R40 single phase cast resin line inductor 40 A 5,5 kW / 7,5 CV 0,549
R50 single phase cast resin line inductor 50 A 6,5 kW / 8,7 CV 0,439
R63 single phase cast resin line inductor 63 A 7,5 kW / 10 CV 0,349
R80 single phase cast resin line inductor 80 A 11 kW / 15 CV 0,275
R100 single phase cast resin line inductor 100 A 14 kW / 18,7 CV 0,220

Dimensions and weights

Reference In (A) Dimensions mm Weight kg Fig
A B C D E Ø
R2.5 2,5 A 50 97 84 80 34 6 0.76 1
R4 4 A 50 97 84 80 34 6 0.78 1
R5 5 A 50 97 94 80 34 6 0.94 1
R6.3 6,3 A 75 96 95 80 56 6 1.3 1
R8 8 A 75 96 95 80 56 6 1.3 1
R10 10 A 75 96 95 80 56 6 1.3 1
R12.5 12,5 A 75 96 95 80 56 6 1.3 1
R16 16 A 75 96 110 80 56 6 1.8 1
R20 20 A 84 102 120 86 65 6 2.7 1
R25 25 A 96 112 126 96 77 6 2.8 1
R31.5 31,5 A 96 112 126 96 77 6 2.9 1
R40 40 A 108 122 155 106 89 6 5 1
R50 50 A 126 145 167 125 102 6 5.6 2
R63 63 A 126 145 187 125 102 7 8.1 2
R80 80 A 126 145 187 125 102 7 8.3 2
R100 100 A 150 165 200 145 125 7 10.6 2

Technical characteristics

Isolation Class B - 130º C
Winding Clase HC - 200ºC
Cover Cast resin
Frequency 50-60 Hz
Protection degree IP-20
Includes Thermal protection against over temperature
Standards IEC/EN/UNE-EN 60076-6, CE
Ambient temperature 40ºC
Line voltage 220 - 260 V
Test voltage 3 kV (1 min, 50 Hz)
  • Voltage drop: 3%
  • Reduction of current harmonics generated by the load, resulting in energy consumption reduction and power factor improvement
  • Reduction of the crest factor of the current wave, extending the lifetime of the equipment and avoiding breakdowns
  • Attenuation of microcuts in the supply voltage generated by power converters, causing malfuntioning of computers, PLC's and other sensitive equipment

Related content

Please register or login to see all documents and information related to this item
Declaration of Conformity CE (PR-R-RTL-RTLX-RTFX-RTOX)