TH - Single phase cast resin medical isolation transformer (EN 61558-2-15)

Standards certificate EN 61558-2-15. Input 230 V · Output 230 V.

Series: 
TH
Single phase cast resin medical isolation transformer (EN 61558-2-15)
If you need more information you can contact us. If you are not logged in you can log in here
  • Link to accessories for medical isolating transformers
  • With certificate according to the Standards IEC/EN 61558-2-15
  • Advantages of cast resin technique:
    • Protection against corrosive environments
    • Suitable for elevated vibration levels
    • No damange of wire isolation due to current peaks
    • Reduction of noise and internal vibrations

Products in this family

Reference Description Rating Input voltage Output voltage
TH1000 Medical isolation transformer 1000 VA 230 V 230 V
TH2000 Medical isolation transformer 2000 VA 230 V 230 V
TH3150 Medical isolation transformer 3150 VA 230 V 230 V
TH4000 Medical isolation transformer 4000 VA 230 V 230 V
TH5000 Medical isolation transformer 5000 VA 230 V 230 V
TH6300 Medical isolation transformer 6300 VA 230 V 230 V
TH8000 Medical isolation transformer 8000 VA 230 V 230 V
TH10000 Medical isolation transformer 10000 VA 230 V 230 V

Dimensions and weights

Reference Description Rating Dimensions mm Weight kg Fig
A B C D E Ø
TH1000 Medical isolation transformer 1000 VA 190 180 205 115 160 9 21.7
TH2000 Medical isolation transformer 2000 VA 240 180 255 106 210 9 31.8
TH3150 Medical isolation transformer 3150 VA 240 230 255 126 210 9 40.2
TH4000 Medical isolation transformer 4000 VA 240 235 255 136 210 9 43.6
TH5000 Medical isolation transformer 5000 VA 290 230 305 116 260 11 56
TH6300 Medical isolation transformer 6300 VA 290 240 305 136 260 11 65
TH8000 Medical isolation transformer 8000 VA 340 290 355 142 310 11 85
TH10000 Medical isolation transformer 10000 VA 340 310 355 162 310 11 99

Technical characteristics

Isolation Class F - 155ºC
Winding Class HC - 200ºC
Leakage current
< 0,5 mA secondary-earth
< 3,5 mA cover-earth
Cover Cast resin
Frequency 50-60 Hz
Protection degree
IP-20
Includes Electrostatic screen between primary and secondary
Bimetal thermal protection
Standards IEC/EN 61558-1 / 61558-2-15 CE
Safety class
Class I
Test voltage
3,5 kV (1 min, 50 Hz)