Reference Description Rating Input voltage Output voltage
TTHX1 Medical isolation transformer 1 kVA 400 V + N 230 V + N
TTHX2 Medical isolation transformer 2 kVA 400 V + N 230 V + N
TTHX3.15 Medical isolation transformer 3.15 kVA 400 V + N 230 V + N
TTHX4 Medical isolation transformer 4 kVA 400 V + N 230 V + N
TTHX5 Medical isolation transformer 5 kVA 400 V + N 230 V + N
TTHX6.3 Medical isolation transformer 6.3 kVA 400 V + N 230 V + N
TTHX8 Medical isolation transformer 8 kVA 400 V + N 230 V + N
TTHX10 Medical isolation transformer 10 kVA 400 V + N 230 V + N

Dimensions and weights

Reference Description Rating Dimensions mm Weight kg Fig
A B C D E Ø
TTHX1 Medical isolation transformer 1 kVA 240 108 253 80 200 9 16
TTHX2 Medical isolation transformer 2 kVA 240 128 253 100 200 9 22
TTHX3.15 Medical isolation transformer 3.15 kVA 300 124 303 96 250 9 27.5
TTHX4 Medical isolation transformer 4 kVA 300 134 303 106 250 9 29.5
TTHX5 Medical isolation transformer 5 kVA 300 154 303 126 250 9 47.9
TTHX6.3 Medical isolation transformer 6.3 kVA 300 164 303 136 250 9 52
TTHX8 Medical isolation transformer 8 kVA 360 144 353 116 300 11 64
TTHX10 Medical isolation transformer 10 kVA 360 164 353 136 300 11 78

Technical characteristics

Isolation Class F - 155ºC
Winding Class HC - 200ºC
Leakage current
< 0,5 mA secondary-earth
< 3,5 mA cover-earth
Frequency 50-60 Hz
Protection degree
IP-00
Connection group YNyn0
Includes Electrostatic screen betweeen primary and secondary
Bimetal thermal protection
Standards IEC/EN 61558-1 / 61558-2-15 CE
Safety class
Class I
Test voltage
4,5 kV (1 min, 50 Hz)